Technical Features

Input power kW 6, 9, 12, 15, 18, 21, 24 (Models Ray 6 – 24 K)
Efficiency - 99.5%
Power - 220V or 415V, 50Hz (only 6, 9, 12kW versions available in 220V)
Electrical current max. for 24kW version is 3 x 36 A
Level of electrical protection IP 40
Min. / Max. pressure of heating water kPa 100 / 300 (1 to 3 bar)
Max. operational temperature of output heating water is 85°C
Internal expansion vessel volume 10 litres
Weight approx. 34kg
Electronic soft start technology provides acceptable electrical load to supply network. Load increments never exceed 6kW, and 2kW / phase for the 3 phase versions.
The circulating-water pump is in operation for the minimum necessary time, thus saving energy and reducing mechanical wear.
Pump run-on evacuates remaining hot water from boiler to save energy after it is switched off.
Occasional pump spin-up during inactive periods stops pump mechanism sticking.
The boiler's hydroblock is a modern unit, also used for gas boilers. It contains a pump with an automatic air vent, a pressure sensor for the heating water, a safety valve and tundish discharge and a connection to the internal 10-litre expansion vessel.
Easy connection to Guernsey Electricity's Economy tariffs via a 2 wire connection to the 'volt free' ripple control connection on the meter + normal supply cable.
Flow Rate
Development and manufacture of PROTHERM boilers is certified according to the international quality standard ISO 9001. These boilers also have CE certification.

Dimensions

Water treatment

Use normal anti-corrosion agents in central heating water - ideal pH is 7.

HTML generated on 24/09/2008 16:02:04 by MacroHTML from CGI Systems